Error Message Reference
The following table maps common S7 error strings to their likely cause and fix.
Error message |
Likely cause |
Fix |
|---|---|---|
|
PUT/GET communication is not enabled on the PLC, or the data block still has optimized block access enabled. |
Enable PUT/GET in TIA Portal and disable optimized block access on each DB. See TIA Portal Configuration. |
|
The requested function is not supported on this PLC model. S7-1200 and S7-1500 PLCs restrict certain operations. |
Check Siemens documentation for your PLC model. Some functions are only available on S7-300/400. |
|
Wrong DB number, the DB does not exist, or the address is out of range. |
Verify the DB number exists on the PLC and that the offset and size are within bounds. |
|
Reading or writing past the end of a DB or memory area. |
Check the DB size in TIA Portal and ensure |
|
The PLC has password protection enabled. |
Remove or lower the protection level in TIA Portal under Protection & Security. |
|
Network issue: PLC is unreachable, a firewall is blocking port 102, or the PLC is not responding. |
Check network connectivity ( |
|
Same as above. |
Same as above. |
|
The PLC is not reachable on the network. |
Verify IP address, subnet, and routing. Ensure the PLC Ethernet port is connected and configured. |
|
The connection to the PLC was lost unexpectedly. |
The PLC may have been restarted, the cable disconnected, or another client took over the connection. See Connection Issues. |